• RS-3000/RS-3500 FAP-BZ detects leak of almost every kind of liquid by optical-electrical method.
• Either standalone use, or interfaced with a Control Unit is available by choice for application to the same Detection Unit.
• The case material of Detection Unit is featured by PFA, resisting against corrosive liquids or atmosphere, and complete water-protected feature of sound loud hole is fabricated.
• Quick detection by spot where the liquid leakage occurs.
• RS-3000BZ is suitable for the large scale and complex factory.
• Alarm beep freeze when detection are taken out of Bracket.
• In a complex and large factory, “sound” saves time for locating, where the leakage happens.
• All the same splendid features as those of RS-3000-BZ.
• RS-3500-BZ has been developed to propose PNP configuration circuit application, even. RS-3000-BZ is NPN configuration.
• RS-3500 matches with safety circuit design of zero voltage common grounded as PNP configuration is so.
• Using Control unit of RS-3500C, you can choose a neutral relay contact output. Furthermore RS-3500C provides a logically accumulated output from 8 input signal sources to one output; this is the same idea of RS-3000C.
Model | RS-3000FAP-BZ | RS-3500FAP-BZ | ||||
Supply Voltage | DC 24V ±10% | |||||
Power Consumption | 30mA or Below | |||||
Output Configuration | NPN Open Collector, 50mA max., Single | PNP Open Collector, 50mA max., Single | ||||
Functions | LED Light Display | Buzzer | Output Signal | |||
Normal Status | Green Stable ON | OFF | ON | |||
Leak Status | Red Flicker ON | ON | OFF | |||
Wrong Location | Red Flicker ON | OFF | OFF | |||
Consume Current | Available with RS-3000C | Available with RS-3500C | ||||
Ambient Temperature | -10°C to 60°C | |||||
Material | Case | PFA | ||||
Cable | FEP, 3-wire sheath | |||||
Water Protection | Sealed structure, equivalent IP67 (IEC) | |||||
Weight | Approx. 55g | |||||
Absorbent Paper | Not Required | |||||
Bracket*1 | P/N-6716 (Stainless Steel), or P/N 6720B (PVC) | |||||
Cable Length*2 | 2m (standard), 5m (optional) *2 |
*1 When ordering, designate with suffix code (-6716) or (-6720B) at the last row of code number of the model to define the attached accessary of Bracket
*2 If optional 5m cable length is required, add the suffix code of -5m into the code number between the –BZ and above bracket code. Eg. RS-3000FAP-BZ-5m(-6716)